Cách sử dụng đồng hồ vạn năng để tìm đoản mạch?
Short-circuit measurement is very common in electrical maintenance and component fault location. When measuring short-circuit faults, be sure to disconnect the power supply, and remember not to operate with power on. For short-circuit measurement, use the buzzer or ohm profile of the multimeter to measure. The buzzer is used to measure more intuitively. When the line is short-circuited, the multimeter will "buzz" directly. The principle of buzzer is when the measured resistance is less than about 75Ω, the multimeter A beep occurs. If you want to know the resistance value between the two lines more accurately, you can use the 200Ω measurement. Using the buzzer mode to measure, sometimes the actual internal resistance between the two signals is small, it is easy to misjudge, such as relay/contactor coil, many relays/contactor coil impedance is less than 75Ω, using the buzzer mode measurement will The buzzer sounds like a short circuit, but it doesn't.
Các kỹ sư thường sử dụng còi của đồng hồ vạn năng để nhanh chóng tìm ra điểm - ngắn mạch của đường dây hoặc linh kiện, chẳng hạn như đo điện trở và tụ điện có bị ngắn mạch - hay không, điốt có bị đứt ngược hay không. xuống, liệu triode có bị hỏng hay không (khi triode bị hỏng, đế và bộ phát thường bị ngắn mạch -), Cho dù có đoản mạch giữa nguồn điện và mặt đất của chip mạch tích hợp hay không, có đoản mạch giữa hai chân hay không, v.v.